- Number of Main Contacts NO
- 4
- Number of Main Contacts NC
- 0
- Number of Auxiliary Contacts NO
- 0
- Number of Auxiliary Contacts NC
- 0
- Number of Poles
- 4P
- Standards
- IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CAN/CSA C22.2 No.60947-1, CAN/CSA C22.2 No.60947-4-1
- Rated Operational Voltage
- Main Circuit 690 V
- Rated Frequency (f)
- Control Circuit 50 / 60 Hz · Main Circuit 50 / 60 Hz
- Conventional Free-air Thermal Current (Ith)
- acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A
- Rated Operational Current AC-1 (Ie)
- (690 V) 40 °C 25 A · (690 V) 60 °C 25 A · (690 V) 70 °C 22 A
- Rated Operational Current AC-3 (Ie)
- (415 V) 60 °C 9 A · (440 V) 60 °C 9 A · (500 V) 60 °C 9.5 A · (690 V) 60 °C 7 A · (380 / 400 V) 60 °C 9 A · (220 / 230 / 240 V) 60 °C 9 A
- Rated Operational Current DC-1 (Ie)
- (110 V) 1-Pole, 40 °C 10 A · (110 V) 1-Pole, 60 °C 10 A · (110 V) 1-Pole, 70 °C 10 A · (110 V) 2 Poles in Series, 40 °C 25 A · (110 V) 2 Poles in Series, 60 °C 25 A · (110 V) 2 Poles in Series, 70 °C 22 A · (110 V) 3 Poles in Series, 40 °C 25 A · (110 V) 3 Poles in Series, 60 °C 25 A · (110 V) 3 Poles in Series, 70 °C 22 A · (110 V) 4 Poles in Series, 40 °C 25 A · (110 V) 4 Poles in Series, 60 °C 25 A · (110 V) 4 Poles in Series, 70 °C 22 A · (220 V) 2 Poles in Series, 40 °C 10 A · (220 V) 2 Poles in Series, 60 °C 10 A · (220 V) 2 Poles in Series, 70 °C 10 A · (220 V) 3 Poles in Series, 40 °C 25 A · (220 V) 3 Poles in Series, 60 °C 25 A · (220 V) 3 Poles in Series, 70 °C 22 A · (220 V) 4 Poles in Series, 40 °C 25 A · (220 V) 4 Poles in Series, 60 °C 25 A · (220 V) 4 Poles in Series, 70 °C 22 A · (440 V) 4 Poles in Series, 40 °C 10 A · (440 V) 4 Poles in Series, 60 °C 10 A · (440 V) 4 Poles in Series, 70 °C 10 A · (72 V) 1-Pole, 40 °C 25 A · (72 V) 1-Pole, 60 °C 25 A · (72 V) 1-Pole, 70 °C 22 A · (72 V) 2 Poles in Series, 40 °C 25 A · (72 V) 2 Poles in Series, 60 °C 25 A · (72 V) 2 Poles in Series, 70 °C 22 A · (72 V) 3 Poles in Series, 40 °C 25 A · (72 V) 3 Poles in Series, 60 °C 25 A · (72 V) 3 Poles in Series, 70 °C 22 A · (72 V) 4 Poles in Series, 40 °C 25 A · (72 V) 4 Poles in Series, 60 °C 25 A · (72 V) 4 Poles in Series, 70 °C 22 A
- Rated Operational Current DC-3 (Ie)
- (110 V) 1-Pole, 40 °C 6 A · (110 V) 1-Pole, 60 °C 6 A · (110 V) 1-Pole, 70 °C 6 A · (110 V) 2 Poles in Series, 40 °C 25 A · (110 V) 2 Poles in Series, 60 °C 25 A · (110 V) 2 Poles in Series, 70 °C 22 A · (110 V) 3 Poles in Series, 40 °C 25 A · (110 V) 3 Poles in Series, 60 °C 25 A · (110 V) 3 Poles in Series, 70 °C 22 A · (110 V) 4 Poles in Series, 40 °C 25 A · (110 V) 4 Poles in Series, 60 °C 25 A · (110 V) 4 Poles in Series, 70 °C 22 A · (220 V) 2 Poles in Series, 40 °C 6 A · (220 V) 2 Poles in Series, 60 °C 6 A · (220 V) 2 Poles in Series, 70 °C 6 A · (220 V) 3 Poles in Series, 40 °C 25 A · (220 V) 3 Poles in Series, 60 °C 25 A · (220 V) 3 Poles in Series, 70 °C 22 A · (220 V) 4 Poles in Series, 40 °C 25 A · (220 V) 4 Poles in Series, 60 °C 25 A · (220 V) 4 Poles in Series, 70 °C 22 A · (440 V) 4 Poles in Series, 40 °C 6 A · (440 V) 4 Poles in Series, 60 °C 6 A · (440 V) 4 Poles in Series, 70 °C 6 A · (72 V) 1-Pole, 40 °C 25 A · (72 V) 1-Pole, 60 °C 25 A · (72 V) 1-Pole, 70 °C 22 A · (72 V) 2 Poles in Series, 40 °C 25 A · (72 V) 2 Poles in Series, 60 °C 25 A · (72 V) 2 Poles in Series, 70 °C 22 A · (72 V) 3 Poles in Series, 40 °C 25 A · (72 V) 3 Poles in Series, 60 °C 25 A · (72 V) 3 Poles in Series, 70 °C 22 A · (72 V) 4 Poles in Series, 40 °C 25 A · (72 V) 4 Poles in Series, 60 °C 25 A · (72 V) 4 Poles in Series, 70 °C 22 A
- Rated Operational Current DC-5 (Ie)
- (110 V) 1-Pole, 40 °C 4 A · (110 V) 1-Pole, 60 °C 4 A · (110 V) 1-Pole, 70 °C 4 A · (110 V) 2 Poles in Series, 40 °C 10 A · (110 V) 2 Poles in Series, 60 °C 10 A · (110 V) 2 Poles in Series, 70 °C 10 A · (110 V) 3 Poles in Series, 40 °C 25 A · (110 V) 3 Poles in Series, 60 °C 25 A · (110 V) 3 Poles in Series, 70 °C 22 A · (110 V) 4 Poles in Series, 40 °C 25 A · (110 V) 4 Poles in Series, 60 °C 25 A · (110 V) 4 Poles in Series, 70 °C 22 A · (220 V) 2 Poles in Series, 40 °C 4 A · (220 V) 2 Poles in Series, 60 °C 4 A · (220 V) 2 Poles in Series, 70 °C 4 A · (220 V) 3 Poles in Series, 40 °C 9 A · (220 V) 3 Poles in Series, 60 °C 9 A · (220 V) 3 Poles in Series, 70 °C 9 A · (220 V) 4 Poles in Series, 40 °C 10 A · (220 V) 4 Poles in Series, 60 °C 10 A · (220 V) 4 Poles in Series, 70 °C 10 A · (440 V) 4 Poles in Series, 40 °C 4 A · (440 V) 4 Poles in Series, 60 °C 4 A · (440 V) 4 Poles in Series, 70 °C 4 A · (72 V) 1-Pole, 40 °C 9 A · (72 V) 1-Pole, 60 °C 9 A · (72 V) 1-Pole, 70 °C 9 A · (72 V) 2 Poles in Series, 40 °C 25 A · (72 V) 2 Poles in Series, 60 °C 25 A · (72 V) 2 Poles in Series, 70 °C 22 A · (72 V) 3 Poles in Series, 40 °C 25 A · (72 V) 3 Poles in Series, 60 °C 25 A · (72 V) 3 Poles in Series, 70 °C 22 A · (72 V) 4 Poles in Series, 40 °C 25 A · (72 V) 4 Poles in Series, 60 °C 25 A · (72 V) 4 Poles in Series, 70 °C 22 A
- Rated Operational Power AC-3 (Pe)
- (400 V) 4 kW · (415 V) 4 kW · (440 V) 4 kW · (500 V) 5.5 kW · (690 V) 5.5 kW · (380 / 400 V) 4 kW · (220 / 230 / 240 V) 2.2 kW
- Rated Short-time Withstand Current Low Voltage (Icw)
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A · at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A · at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A · at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A · at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
- Maximum Breaking Capacity
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A · cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
- Rated Insulation Voltage (Ui)
- acc. to IEC 60947-4-1 690 V · acc. to UL/CSA 600 V
- Rated Impulse Withstand Voltage (Uimp)
- 6 kV
- Maximum Electrical Switching Frequency
- (AC-1) 600 cycles per hour
- Maximum Mechanical Switching Frequency
- 3600 cycles per hour
- Rated Control Circuit Voltage (Uc)
- 50 Hz 100 ... 250 V · 60 Hz 100 ... 250 V · DC Operation 100 ... 250 V
- Power Loss
- at Rated Operating Conditions AC-1 per Pole 0.8 W · at Rated Operating Conditions AC-3 per Pole 0.1 W
- Operate Time
- Between Coil De-energization and NC Contact Closing 13 ... 98 ms · Between Coil De-energization and NO Contact Opening 11 ... 95 ms · Between Coil Energization and NC Contact Opening 38 ... 90 ms · Between Coil Energization and NO Contact Closing 40 ... 95 ms
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 · TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting by Screws (not supplied)
- 2 x M4 Screws Placed Diagonally
- Connecting Capacity Main Circuit
- Flexible with Ferrule 1/2x 0.75 ... 6 mm² · Flexible with Insulated Ferrule 1x 0.75 ... 4 mm² · Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² · Rigid Solid 1/2x 1 ... 4 mm² · Rigid Stranded 1/2x 1 ... 6 mm²
- Connecting Capacity Auxiliary Circuit
- Rigid Solid 1/2x 1 ... 2.5 mm² · Rigid Stranded 1/2x 1 ... 2.5 mm²
- Connecting Capacity Control Circuit
- Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² · Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² · Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² · Rigid Solid 1/2x 1 ... 2.5 mm² · Rigid Stranded 1/2x 1 ... 2.5 mm²
- Wire Stripping Length
- Control Circuit 10 mm · Main Circuit 10 mm
- Degree of Protection
- acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 · acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
- Tightening Torque
- Control Circuit 1.2 N·m · Main Circuit 1.5 N·m
- Terminal Type
- Screw Terminals
- Product Name
- Block Contactor
- Product Net Width
- 45 mm
- Product Net Depth / Length
- 77 mm
- Product Net Height
- 86 mm
- Product Net Weight
- 0.27 kg